Recently Bureau of Indian Standards issued the Fourth revision of IS 1180 (Part 1): Outdoor Type Oil Immersed Distribution Transformers upto 2500 kVA, 33KV Specification. To discuss the various changes in design parameters of IS we had arranged a technical session in our office on dtd. 20.09.2014.
This session was headed by Mr. Arun Kumar (VP) having the vast experience in electrical & mechanical designing of transformer and previously he had served in BHEL, Haridwar as a design Head, Mr. Sandeep Kumar (AGM Design) & Mr. Gaurav Jain (Sr. Manager Marketing) have also attended the technical session to discuss the technical parameters which are defined in revised IS 1180. Our MD Mr. Girish Kumar also attended the technical session and also gives their valuable inputs in technical session.
In this technical session we have discussed the different categories in which transformers have been divided, which are as below.In revised IS 1180 there are three energy efficiency levels and for each categories, maximum values of total losses have been defined on 50% load and 100% load. Losses & percentage value of impedance for different categories are as below:
a) Three phase distribution transformers upto and including 200 KVA, 11KV Class
Sl. No.
|
Rating (KVA)
|
% Z
|
Energy Efficiency Level 1
|
Energy Efficiency Level 2
|
Energy Efficiency Level 3
|
|||
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
|||
1
|
16 KVA
|
4.5%
|
150W
|
480W
|
135W
|
440W
|
120W
|
400W
|
2
|
25 KVA
|
4.5%
|
210W
|
695W
|
190W
|
635W
|
175W
|
595W
|
3
|
63 KVA
|
4.5%
|
380W
|
1250W
|
340W
|
1140W
|
300W
|
1050W
|
4
|
100 KVA
|
4.5%
|
520W
|
1800W
|
475W
|
1650W
|
435W
|
1500W
|
5
|
160KVA
|
4.5%
|
770W
|
2200W
|
670W
|
1950W
|
570W
|
1700W
|
6
|
200KVA
|
4.5%
|
890W
|
2700W
|
780W
|
2300W
|
670W
|
2100W
|
b) Three phase distribution transformers Higher than 200 KVA upto and including 2500 KVA, 11KV Class
Sl. No.
|
Rating (KVA)
|
% Z
|
Energy Efficiency Level 1
|
Energy Efficiency Level 2
|
Energy Efficiency Level 3
|
|||
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
|||
1
|
250 KVA
|
4.5%
|
1050W
|
3150W
|
980W
|
2930W
|
920W
|
2700W
|
2
|
315 KVA
|
4.5%
|
1100W
|
3275W
|
1025W
|
3100W
|
955W
|
2750W
|
3
|
400 KVA
|
4.5%
|
1300W
|
3875W
|
1225W
|
3450W
|
1150W
|
3330 W
|
4
|
500 KVA
|
4.5%
|
1600W
|
4750W
|
1510W
|
4300W
|
1430W
|
4100W
|
5
|
630 KVA
|
4.5%
|
2000W
|
5855W
|
1860W
|
5300W
|
1745 W
|
4850W
|
6
|
1000 KVA
|
5.0%
|
3000W
|
9000W
|
2790W
|
7700W
|
2620W
|
7000W
|
7
|
1250 KVA
|
5.0%
|
3600W
|
10750W
|
3300W
|
9200W
|
3220W
|
8400W
|
8
|
1600 KVA
|
6.25%
|
4500W
|
13500W
|
4200W
|
11800W
|
3970W
|
11300W
|
9
|
2000 KVA
|
6.25%
|
5400W
|
17000W
|
5050W
|
15000W
|
4790W
|
14100W
|
10
|
2500 KVA
|
6.25%
|
6500W
|
20000W
|
6150W
|
18500W
|
5900W
|
17500 W
|
c) Single Phase distribution transformers upto and including 25 KVA, 11KV Class
Sl. No.
|
Rating (KVA)
|
% Z
|
Energy Efficiency Level 1
|
Energy Efficiency Level 2
|
Energy Efficiency Level 3
|
|||
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
|||
1
|
5KVA
|
4.0%
|
40W
|
115W
|
35W
|
95W
|
30W
|
75W
|
2
|
10KVA
|
4.0%
|
70W
|
190W
|
60W
|
170W
|
55W
|
150W
|
3
|
16KVA
|
4.0%
|
95W
|
265W
|
82W
|
224W
|
63W
|
190W
|
4
|
25KVA
|
4.0%
|
125W
|
340W
|
110W
|
300W
|
95W
|
260W
|
After study of the above we observe followings points which are important for design of transformers:
1) Mr. Sandeep pointed out that losses of energy efficiency level 1 are equivalent to BEE 3 Star Category, energy efficiency level 2 are equivalent to BEE 4 star category and energy efficiency level 3 are equivalent to 5star category for 3 phase distribution transformer upto 200 KVA transformer for 11KV Class.
2) Mr. Gaurav Jain pointed out that losses in energy efficiency level 1 are less than the losses mentioned in ECBC 2009 for transformers higher than 200 KVA upto and including 2500 KVA for 11KV Class
Further to above our design head also observed that IS 1180 are now also applicable for 22KV & 33KV class transformers, losses values for 22KV & 33KV class transformers shall be applicable as per below clause:
a) For transformers having voltage class above 11KV and upto and including 22KV, the permissible total loss value shall not exceed by 5% of the maximum total losses values mentioned in table b) for 3 phase.
b) For transformers having voltage class above 22KV and upto and including 33KV, the permissible total loss value shall not exceed by 7.5% of the maximum total losses values mentioned in table b) for 3 phase.
c) For transformers having voltage class above 11KV and upto and including 22KV, the permissible total loss value shall not exceed by 7.5% of the maximum total losses values mentioned in table c) for single phase.
d) For transformers having voltage class above 22KV and upto and including 33KV, the permissible total loss value shall not exceed by 5% of the maximum total losses values mentioned in table c) for single phase.
In revised IS 1180 there are also some change in oil & winding temperature rise parameters for each category. It also includes the specification for corrugated type transformers. Since our MD Mr. Girish Kumar & our Organization is always emphasize & committed to saving the energy, so we appreciate the BIS & Government of India for taking this step. It will be a great tool for us to serve the nation by saving energy. SAI Electricals already has models HEFF for Level 1 and shortly will come up with models of transformers for Level 2 & Level 3.